Motor soft starter VMX series soft starter setting record

table VMX series soft starter setting record table

fn sff003 starting overload nema/ul5 ~ grade 20 510 F004 running overload nema/ul5 ~ 30 level 510 level F005 overload reset 0= manual 1= automatic

2= invalid

10f006 - f009

standby continuation table

fnpcategory function description adjustment range added value factory setting f010 start

/

stop

mode

slope type selection vr= voltage slope

cr= current slope

1= slope 1, 2= slope 2

1=vr1+vr22=cr1+cr2

3=vr1+cr2

4=cr1+vr2

11f011 slope 1 initial torque (VR) 0 ~ 100% line voltage 1% 60% F012 ramp 1 initial torque (CR) 0 ~ 600% motor current 1% 200% f013 ramp 1 acceleration time 1 ~ 120s1s10sf014 ramp 1 maximum current limit 200% ~ 600% motor current 1% 350% f015 ramp 2 initial torque (VR) 0 ~ 100% line voltage 1% 60% f016 ramp 2 initial torque (CR) 0 ~ 600% motor current 1% 200% E017 ramp 2 acceleration time 1 ~ 120s1s10sf018 ramp 2 maximum current limit 200% - 600% motor current 1% 350% f019 inching

mode

mode

inching voltage 5% ~ 100% line voltage 1% 50% F020 inching time 1 ~ 20s1s10sf021 inching current 100% ~ 500% electric electromechanical current 1% 150% F022 step (1) regenerative medicine products

mode

mode

.P> step voltage 0= invalid, Or 10% ~ 100% line voltage

1% 0f023 step time 0.1 ~ 2s0.1s0.8sf024 soft stop

mode

soft stop selection 0= invalid (taxi stop) 1= valid, overload protection

2= valid, No overload protection

10f025 deceleration start voltage 0 ~ 100% output voltage 1% 60% f026 deceleration completion voltage 0 to 1% less than the initial deceleration voltage

1% 30% f027 deceleration time 1 ~ 60s1s10sf028 restart

start

action

Restart delay (sequential start delay)

0= ineffective, Or 1 ~ 999s

1s0f029 standby f030 operation timer

and

clock

control

device model

type

program timer selection 0= invalid 1= minimum time timer

2= maximum time timer

10f031 operation time timing start command 1 ~ 9999min11f032 clock controller start mode

0 = only respond start button command 1= cycle every day

2= cycle every 2 days

3= every 3 days One cycle

4= one cycle every 4 days

5= one cycle every 5 days

6= one cycle every 6 days

7= one cycle every 7 days

8= no cycle event

10 continued table

fn\\pcategory function description adjustment range added value factory settings f033 operation timing

device and

clock

p> control

mold

type

Event 1 start time 00.00 ~ 23.59 or none 1 no f034 event 2 start time 00.00 ~ 23.59 or none 1 no f035 event 3 starting time 00.00 ~ 23.59 or no 1 no f036 event 4 starting time 00.00 ~ 23.59 or no 1 no f037 event 5 starting time 00.00 ~ 23.59 or no 1 no f038 event 6 starting time 00.00 ~ 23.59 or no 1 no f039 event 7. The verification point selects the starting time 00.00 ~ 23.59 or no 1 no F040 current

and

grounding

according to the interval of 2:5:10, so

barrier

protection

protection

current unbalance trip 0= invalid, Or 5% ~ 30% unbalanced 1% 0f041 current unbalanced tripping delay 1 ~ 20s1s2sf042 overcurrent tripping 0= invalid, or 100% ~ 300% fla1% 0f043 overcurrent tripping delay 1 ~ 20s1s1sf044 low current tripping 0= invalid, or 10% ~ 90% fla1% 0f045 low current tripping delay 1 ~ 60s1s2sf046 ground fault tripping 5% ~ 90% CT ratio 1% 0f047 ground fault tripping delay 1 ~ 60s1s2sf048 locked

Reset

position

and

internal

protection

protection

sliding time lock 0= invalid, or 1 ~ 60mim1min0f049 maximum starting times per hour 0= invalid, or 1 ~ 10 10f050 minimum starting interval 0= invalid, or 1 ~ 60min1min0f051 internal protection set 1 ~ 63163f052 automatic reset fault 1 ~ 1214f053 under specific fault.Automatic restart 0= invalid, Or 1 ~ 10 times 11f054 restart delay 0 ~ 999min10f055 sliding time 1 ~ 3600s10f056 hourly starting time 1 ~ 3600s10f057 hourly starting times 1 ~ 10 times 10f058 starting interval 1 ~ 3600s10f059 thermal capacity 0 ~ 100% 10f060 output

relay

Electric

device

auxiliary relay 1 set 1 ~ 2611f061 auxiliary relay 1 set 1 ~ 2612f062 auxiliary relay 1 set 1 ~ 26116f063 auxiliary relay delay 0= invalid, Or 1 ~ 999s1s0f064 standby f065 communication

communication 0= invalid 1= valid (11 bits)

2= valid (10 bits)

10f066 baud rate 4.8, 9.6 and 19.2kb39.6kbf067modbus address 1 ~ 24711f068 remote start control 0= invalid 1= valid, dual control

2= valid, This control is invalid

10f069 spare continuation table

fn\category function description adjustment range added value factory setting f070 system

setting

user password 0 ~ 999, 0= no password protection 10f071 system reset/reset 0= invalid 1= thermal overload and locking time

reset

2= reset to factory setting

10f072 manufacturer uses f073 current level 18 ~ 99.5501 according to model f074ta ratio 40 ~ 12005 according to model f075 2000 ~ 20471 2000 f076 January 1 ~ 121 January 1f077 January ~ 311 1f078 hours 0 ~ 231h0f079 minutes 0 ~ 591min0f080 downstream demand capacity is less than seconds 0 ~ 591s0f081 version - the manufacturer sets f082-f084

standby f085 fault

record

record

and

operation

line

number

Data

.

fault record 10= no fault record with obvious advantages, Or fault number 1 ~ 27

10f086 fault record 1 time 00.00 ~ 23.5900.0100.00f087 fault record 1 date 01.01 ~ 12.3100.0101.01f088 fault record 20= no fault record, or fault number 1 ~ 27

10f089 fault record 2 time 00.00 ~ 23.5900.0100.00f090 fault record 2 date 01.01 ~ 12.3100.0101.01f091 fault record 30= no fault record, Or fault number 1 ~ 27

10f092 fault record 3 time 00.00 ~ 23.5900.0100.00f093 fault record 3 date 01.01 ~ 12.3100.0101.01f094 operation time, hour 000.0 ~ 999.9h0.1h0f095 operation time, thousand hour 0000 ~ 9999 thousand H1 thousand h0f096 operation cycle 0000 ~ 9999 times 1 time 0f097 operation cycle, 10000 ~ 9999 10000 times 10000 times 0

figure special motor application - two-way double speed